Get in Touch

Call us or email with your enquiry and we can get the right product for you.

DH 30AXP TTW through the wall dehumidifier with 2kW resistance heater option.

Overview

• Airflow: 420m³/h
• Dehumidification @ 30°C, 60% RH = 1.25 L/H

Product Code: 482150-1
Details
DEHUMIDIFICATIONL/hr1.25
L/day 30
TOTAL HEAT TO AIR :-
DEHUMIDIFIER ONLY kW 1.9
DEHUM' & RESISTANCE HEATER kW 2.89
RESISTANCE HEATER ONLY kW 2
DEHUM' & LPHW kW n/a
LPHW ONLY kW n/a
NOMINAL POWER CONSUMED:-
FAN ONLY kW 0.05
DEHUM' (COMP & FAN) kW 0.75
DEHUM & HEATER kW 2.75
HEATER & FAN kW 2.05
SUPPLY 230V 50Hz
FUSE AMP 20
NOMINAL RUNNING AMP 11.7
FULL LOAD AMPS AMP 12.7
COMPRESSOR L.R.A. AMP 15.8
AIR FLOW m3/h 420
NOISE LEVEL @ 3m dB(A) 46
LPHW FLOW RATE L/min n/a
LPHW PRESSURE DROP m hd n/a
HERMETIC SYSTEM
REFRIGERANT CHARGE kg R40?C 0.5(30AP)
0.45(30AXP)
WEIGTH (UNPACKED/PACKED) kg 45 / 55

The DH30AX is an ideal wall mounted unit for dehumidification and condensation control in commercial premises and industrial environments

Features

  • Self contained with fully automatic operation
  • Integral humidistat
  • Polyester coated evaporator and condenser
  • Plastisol coated galvanised steel cabinet
  • Hot gas defrost for low temperature operation
  • Quiet centrifugal fans
  • Remote humidistat and on/off function

Option

  • Electric air heater
  • Floor stand kit

Applications

  • Drying rooms
  • Modular buildings
  • Electrical sub-stations
  • Sports clubs and changing rooms
  • Warehousing and storage
  • Museums, libraries and galleries
  • Garages
Additional Details
Additional Details
Delivery This item is usually built to order. Enquire on 01729 824108
Brand Calorex
Warranty 1 year manufacturers warranty
THROUGH THE WALL DEHUMIDIFIERS manual.pdf (0.9MB)