Flatline 3000 LW
The Mark FLATLINE LW compact heat recovery unit represents an optimal choice for energy-efficient ventilation and the maintenance of a comfortable indoor environment. This unit features a counterflow plate exchanger that achieves a heat recovery efficiency of 90%, allowing for 90% of the extracted energy to be transferred to the incoming fresh air. As a result of this high efficiency, additional heating is typically unnecessary in most scenarios.
Factory-tested and delivered as a Plug & Play solution, the ceiling heat recovery units are versatile and suitable for various applications, including offices, showrooms, apartment complexes, and educational institutions. Their low profile makes them particularly well-suited for installation above suspended ceilings. The Mark FLATLINE LW is designed as a decentralized heat recovery unit, and the mechanical integrity of its casing has been verified in accordance with NEN-EN 1886 standards.
• Deflection: Class D3
• Air leakage: Class L2
• Thermal transmission: Class T4
• Thermal bridging: Class TB4
Product range features
- Quiet
- Compact and standard designs
- Double-walled insulated aluminum AlMg3 casing
- Aluminum counterflow heat exchanger
- Bypass for night ventilation and cooling
- EC fans
- Integrated Plug&Play control
- Can be connected to GBS, BACnet or Modbus via the internet.
- Air quantities from 400-3200m3/h
- Efficiency >90%
- Indoor installation
- Supply filter ePM1 55%
- Drain filter ePM10 75%
- Filter pressure monitoring
- On/off contact
- Fire contact
- Available from stock
Optional:
• Water-Supplied Heating Battery
• Water-supplied cooling system
• Damper section
• Channel progression from rectangular to round
• Louvered dampers for supply and discharge sides
• Constant pressure control (supply)
• CO2 control (not in combination with pressure control)
• Room temperature control
Specification
| FlatLine LW | 3000 | |
| Maximum air amount | m3 /h | 3000 |
| Maximum external pressure | Pa | 300 |
| Efficiency up to | % | 90 |
| Total power consumption per unit | KW | 1,54 |
| Max power consumption per unit | KW | 2 |
| Nominal per unit | A | 7,12 |
| Max power consumption per unit | A | 9,4 |
| Sound pressure level1 | dB(A) | 47 |
| Supply voltage (50hz)1 | V | 1-230 |
| Dimensions | L x W x H mm | 2340 x 1890 x 490 |
| 1 on a 5 meter free field at Pextern is 100Pa | ||
| Delivery | This item is stocked overseas. Please contact the office for leadtime. |
|---|---|
| Brand | Mark |
| Warranty | 1 year warrenty in compliance with ORGALIME S2000 |